Evaluation and user’s perception regarding the thermal comfort and air quality in operable glazed balconies located in an urban industrialized region

Authors

DOI:

https://doi.org/10.11606/gtp.v13i3.148455

Keywords:

Environmental evaluation, Residential building, Balconies, Thermal comfort, Air quality

Abstract

Currently, a very common action in large cities is closing the residential balconies with operable glass. In the city of Vitoria, ES, it is constant the residents' complaint about the presence of black dust in their residences. The nuisance caused by the presence of this particulate matter is the main motivator of the practice of closing balconies in the region. The aim of the present research was to evaluate the environmental quality and the Vitoria resident’s perception – regarding the thermal comfort and air quality – who lives in apartments with and with no operable glazed balconies. From the setting of criteria and the subsequent choice of a strategically located residential condominium, the methodology used has been established considering two main sources of obtaining data and information: directly from users, through the application of questionnaires; and by field measurements of the air temperature, air relative humidity and concentration of particulate matter. The results show that the daily average concentration of particulates was higher in situation of the operable glazed balcony was closed than in the open condition. In addition, the use of operable glazed balconies, keeping them closed most of the time leads to increased air temperature in the environment and thermal discomfort, which causes some residents have recourse to the use of air conditioner, thus subverting the original purpose of the balcony in hot and humid climates, which is provide shading and natural ventilation to the interior spaces.  

Downloads

Download data is not yet available.

Author Biographies

  • Erica Coelho Pagel, Universidade Vila Velha
    Programa de Pós-Graduação em Arquitetura e Cidade
  • Cristina Engel de Alvarez, Universidade Federal do Espírito Santo

    Departamento de Arquitetura e Urbanismo

    Programa de Pós-Graduação em Arquitetura e Urbanismo

  • Neyval Costa Reis Júnior, Universidade Federal do Espírito Santo

    Departamento de Engenharia Ambiental

    Programa de Pós-Graduação em Engenharia Ambiental

References

ABNT - ASSOCIAÇÃO BRASILEIRA DE NORMAS TÉCNICAS. NBR 15575-1 Edificações Habitacionais — Desempenho Parte 1: Requisitos gerais. Brasil: [s.n.], 2013

ANNESI-MAESANO, Isabella et al. Residential proximity fine particles related to allergic sensitisation and asthma in primary school children. Respiratory Medicine, v. 101, n. 8, p. 1721–1729, 2007.

ANVISA AGÊNCIA NACIONAL DE VIGILâNCIA SANITÁRIA. Resolução - RE no 9, de 16 de janeiro de 2003. Brasil: Diário Oficial da União, 2003

ASHRAE STANDARD. Thermal Environmental Conditions for Human Occupancy. Atlanta: [s.n.], 2013

BARBOSA, Miriam Jerônimo; WEILLER, Giovana Cristiana Buso; LAMBERTS, Roberto. Disposição dos equipamentos para medição da temperatura do ar em edificações. Ambiente Construído, v. 7, n. 48, p. 89–108, 2007.

BRANDÃO, Helena Câmara Lacé; MARTINS, Angela Maria Moreira. A Varanda e suas contribuições para a Sustentabilidade. São Paulo: Núcleo de Pesquisas em Tecnologia da Arquitetura e Urbanismo da Universidade de São Paulo, 2007.

CANDIDO, Christhina; DEAR, Richard De. From thermal boredom to thermal pleasure: a brief literature review. Ambiente Construído, v. 12, p. 81–90, 2012.

CORBELLA, O D Ã; MAGALHA, M A A A. Conceptual differences between the bioclimatic urbanism for Europe and for the tropical humid climate. Renewable Energy, v. 33, p. 1019–1023, 2008.

COUZEMENCO, Fernanda. Pó preto aumenta e população pede socorro ao prefeito de Vitória. Disponível em: <http://seculodiario.com.br >. Acesso em: 27 jun. 2018.

EN ISO - THE EUROPEAN STANDARDIZATION. EN ISO 28802:2012 - Ergonomics of the physical environment - an environmental survey involving. Dublin: National Standards Authority of Ireland. , 2012

FREITAS, Clarice Umbelino de et al. Air pollution and its impacts on health in Vitoria, Espirito Santo, Brazil. Revista de Saúde Pública, v. 50, n. 0, 2016.

G1. Relatório com 191 metas para reduzir pó preto na Grande Vitória é entregue para Vale e ArcelorMittal. Disponível em:<https://g1.globo.com/es >. Acesso em: 27 jun. 2018.

GODISH, Thad. Air Quality. 4th editio ed. Chelsea, Michigan: Lewis Publishers, 2003.

HILLIAHO, Kimmo; NORDQUIST, Birgitta; et al. Energy saving and indoor climate effects of an added glazed facade to a brick wall building : Case study. Journal of Building Engineering, v. 7, p. 246–262, 2016.

HILLIAHO, Kimmo; KOVALAINEN, Ville; et al. Glazed spaces: A simplified calculation method for the evaluation of energy savings and interior temperatures. Energy & Buildings, v. 125, p. 27–44, 2016.

HILLIAHO, Kimmo; LAHDENSIVU, Jukka; VINHA, Juha. Glazed space thermal simulation with IDA-ICE 4 . 61 software — Suitability analysis with case study. Energy & Buildings, v. 89, p. 132–141, 2015.

HILLIAHO, Kimmo; MÄKITALO, Eerik; LAHDENSIVU, Jukka. Energy saving potential of glazed space : Sensitivity analysis. Energy & Buildings, v. 99, p. 87–97, 2015.

IBGE INSTITUTO BRASILEIRO DE GEOGRAFIA E ESTATÍSTICA. Senso 2010. Disponível em: . Acesso em: 6 jun. 2016.

IEMA – INSTITUTO ESTADUAL DE MEIO AMBIENTE E RECURSOS HÍDRICOS. Qualidade do ar. Disponível em: <https://iema.es.gov.br/qualidadedoar>. Acesso em: 22 jun. 2018.

INMET - INSTITUTO NACIONAL DE METEOROLOGIA. Estações automáticas. Disponível em: <http://www.inmet.gov.br/portal/index.php?r=estacoes/estacoesautomaticas>. Acesso em: 7 jan. 2017.

ISO - INTERNATIONAL ORGANIZATION FOR STANDARDIZATION. ISO 7726 - Ergonomics of the thermal environment -- Instruments for measuring physical quantities. . Genove: [s.n.], 1998

JORGE, Liziane De Oliveira. Estrategias de Flexibilidade na Arquitetura Residencial Multifamiliar. 2012. 511 f. Tese de doutorado. Faculdade de Arquitetura e Urbanismo. Universidade de São Paulo, 2012.

MATTIUZZI, Henrique Vescovi; MARCHIORO, Eberval. O comportamento dos ventos em Vitória (ES): a gestão e interpretação dos dados climatológicos. Revista Geonorte, v. 2, n. 4, p. 983–993, 2012.

MELO, Milena M et al. Annoyance Caused by Air Pollution : A Comparative Study of Two Industrialized Regions. v. 9, n. 2, p. 177–182, 2015.

MIOT, Hélio Amante. Tamanho da amostra em estudos clínicos e experimentais. Jornal Vascular Brasileiro, v. 10, n. 4, p. 275–278, 2011.

NICO-RODRIGUES, Edna Aparecida et al. Quando a janela define a condição de desempenho térmico em ambientes ventilados naturalmente: caso específico das edificações multifamiliares em Vitória, ES. Ambiente Construído, v. 15, p. 7–23, 2015.

NICOLUSSI, Francine Heloisa et al. Poluição do ar e doenças respiratórias alérgicas em escolares. Revista de Saúde Pública, v. 48, n. 2, p. 326–330, 2014.

NOBRES, Juirana et al. Entenda o que é o pó preto que polui o ar e o mar de Vitória há anos Samarco , Acellor Mittal e Vale são apontadas como principais poluidoras. Disponível em: <http://g1.globo.com >. Acesso em: 27 jun. 2018.

PAGEL, É.C. et al. Indoor air quality in an Antarctic Research Station: Fungi, particles and aldehyde concentrations associated with building materials and architectural design. Indoor and Built Environment, n.1, p. 1-19, 2017.

PMV PREFEITURA MUNICIPAL DE VITÓRIA. Lei 6801 Seção III do capítulo V da Lei 4821 de 30 de dezembro de 1998. Brasil: [s.n.], 2006

PMV PREFEITURA MUNICIPAL DE VITÓRIA. Lei N° 4821 Código de Edificações do Município de Vitória. Brasil: [s.n.], 1998

SALEH, Philip H. Thermal performance of glazed balconies within heavy weight / thermal mass buildings in Beirut , Lebanon ’ s hot climate. Energy & Buildings, v. 108, p. 291–303, 2015.

SANTOS, J. M. et al. Experimental investigation of outdoor and indoor mean concentrations and concentration fluctuations of pollutants. Atmospheric Environment, v. 45, n. 36, p. 6534–6545, 2011.

SANTOS, Jane Meri et al. Source apportionment of settleable particles in an impacted urban and industrialized region in Brazil. Environmental Science and Pollution Research, v. 24, n. 27, p. 22026–22039, 2017.

SCHIRMER, Waldir Nagel et al. A poluição do ar em ambientes internos e a síndrome dos edifícios doentes. Ciência & Saúde Coletiva, v. 16, n. 8, p. 3583–3590, 2011.

SEINFELD, John H; PANDIS, S N. Atmospheric Chemistry and Physics From Air Pollution to Climate Change. SECOND EDI ed. Hoboken, New Jersey: John Wiley & Sons, Inc., 2006.

SILVA, Marielle Ferreira et al. Post-occupancy evaluation of residential buildings in Luxembourg with centralized and decentralized ventilation systems, focusing on indoor air quality (IAQ): assessment by questionnaires and physical measurements. Energy & Buildings, n. 148, p.119-127, 2017.

TEIXEIRA, Fábio. Prefeito deve sancionar lei que permite o fechamento de varandas. Disponível em: <http://oglobo.globo.com>. Acesso em: 6 jun. 2016.

TOLEDO, Alexandre Marcio; COSTA, Isabely Penina C. da;; BULHÕES, Michelle Carolline S. Usuários fecham as varandas dos apartamentos da Orla de Maceió : adequação aos novos usos ou inadequação ao clima ? Gestão & Tecnologia de Projetos, v. 5, n. 2, p. 131–154, 2010.

Published

2018-12-26

Issue

Section

Papers

How to Cite

PAGEL, Erica Coelho; ALVAREZ, Cristina Engel de; REIS JÚNIOR, Neyval Costa. Evaluation and user’s perception regarding the thermal comfort and air quality in operable glazed balconies located in an urban industrialized region. Gestão & Tecnologia de Projetos (Design Management and Technology), São Carlos, v. 13, n. 3, p. 57–78, 2018. DOI: 10.11606/gtp.v13i3.148455. Disponível em: https://www.revistas.usp.br/gestaodeprojetos/article/view/148455.. Acesso em: 23 may. 2024.